Omron SYSMAC CJ1W-EIP21 Manuel d'utilisateur Page 1

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Logiciel Omron SYSMAC CJ1W-EIP21. Omron SYSMAC CJ1W-EIP21 User's Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 464
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
OPERATION M ANUAL
Cat. No. W465-E1-05
SYSMAC CS and CJ Series
CS1W-EIP21 (100Base-TX)
CJ1W-EIP21 (100Base-TX)
CJ2H-CPU6@-EIP (100Base-TX)
CJ2M-CPU3@ (100Base-TX/10Base-T)
EtherNet/IP Units
Vue de la page 0
1 2 3 4 5 6 ... 463 464

Résumé du contenu

Page 1 - OPERATION M ANUAL

OPERATION M ANUALCat. No. W465-E1-05SYSMAC CS and CJ SeriesCS1W-EIP21 (100Base-TX)CJ1W-EIP21 (100Base-TX)CJ2H-CPU6@-EIP (100Base-TX)CJ2M-CPU3@ (100Bas

Page 2

xTABLE OF CONTENTSAppendicesA CS/CJ-series Ethernet Unit Function Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 375B Eth

Page 3 - EtherNet/IP Units

74CIO Area Allocations Section 4-2Bit Name Status Manipulated byUnit operation0 Unit Error Occurred ON Unit Indicates that an error occurred that is r

Page 4

75CIO Area Allocations Section 4-2Unit Status 2(EtherNet/IP Unit to CPU Unit) (n + 11)10 to 13(Not used) --- --- ---14 Status Area Layout Setting Erro

Page 5 - Trademarks and Copyrights

76CIO Area Allocations Section 4-21 Tag Data Link OperatingON Unit Indicates that the tag data link is operating. Turned OFF when communications stop

Page 6

77CIO Area Allocations Section 4-2Communications Status 1(EtherNet/IP Unit to CPU Unit) (n + 12)Word n+12 contains status flags related to the tag dat

Page 7

78CIO Area Allocations Section 4-24 Invalid Communi-cations ParameterON Unit ON when there was an error in the validation check of tag data link param

Page 8

79CIO Area Allocations Section 4-2Communications Status 2(EtherNet/IP Unit to CPU Unit) (n + 13)Word n+13 contains status flags related to the Etherne

Page 9

80CIO Area Allocations Section 4-2Registered Target Node Table(EtherNet/IP Unit to CPU Unit) (n + 16 to n + 19)Words n+16 to n+19 show the registratio

Page 10 - TABLE OF CONTENTS

81CIO Area Allocations Section 4-2Normal Target Node Table (EtherNet/IP Unit to CPU Unit) (n+20 to n+23)Words n+20 to n+23 show the connection status

Page 11 - About this Manual:

82CIO Area Allocations Section 4-214 FINS/TCP Connec-tion 15ON Unit Turned ON by the Unit when a connection is established.OFF Unit Turned OFF by the

Page 12 - Relevant Manuals

83DM Area Allocations Section 4-34-3 DM Area Allocations4-3-1 Overview of the Allocated DM Area WordsThe various kinds of data are stored in the offse

Page 13

xiAbout this Manual:This manual describes the operation of the CS/CJ-series EtherNet/IP Units and the built-in EtherNet/IPports on a CJ2 CPU Unit for

Page 14

84DM Area Allocations Section 4-3address, even if a non-zero IP address was set in the IP Address Display/Setting Area words beforehand.(2) It is not

Page 15 - LIMITATIONS OF LIABILITY

85User Settings Area Section 4-44-4 User Settings Area4-4-1 Overview of the User Settings AreaWhen the layout of the allocated CIO Area words is set t

Page 16 - Application Considerations

86User Settings Area Section 4-4Normal Target Node Table (EtherNet/IP Unit to CPU Unit)These flags indicate the connection status of the target nodes.

Page 17 - Disclaimers

87User Settings Area Section 4-4Target Node PLC Error Information (EtherNet/IP Unit to CPU Unit)These flags indicate the error status (logical OR of f

Page 18

88Auxiliary Area Data Section 4-54-5 Auxiliary Area DataThe following table and descriptions cover the words and bits in the CPUUnit’s Auxiliary Area

Page 19 - Unit Versions of CS/CJ-series

89Auxiliary Area Data Section 4-54-5-2 Read/Write Bits (User Settings)A417 A41700 to A41715CPU Bus Unit Error, Unit Number FlagsWhen an error occurs i

Page 20 - Unit Versions

90Auxiliary Area Data Section 4-5

Page 21 - PRECAUTIONS

91SECTION 5Determining IP AddressesThis section explains how to manage and use IP addresses.5-1 IP Addresses . . . . . . . . . . . . . . . . . . . . .

Page 22 - 3 Safety Precautions

92IP Addresses Section 5-15-1 IP Addresses5-1-1 IP Address ConfigurationIP addresses are made up of 32 bits of binary data divided into four 8-bit fie

Page 23 - Safety Precautions 3

93IP Addresses Section 5-15-1-3 EtherNet/IP Unit IP Address SettingsAn IP address must be set even for the EtherNet/IP Unit or built-in EtherNet/IPpor

Page 24 - 5 Application Precautions

xiiRelevant ManualsThe following table lists CS- and CJ-series manuals that contain information relevant to EtherNet/IPUnits or built-in EtherNet/IP p

Page 25 - Application Precautions 5

94IP Addresses in FINS Communications Section 5-25-1-5 CIDRCIDR, or classless interdomain routing, is used to assign IP addresses that donot use class

Page 26 - 6-2 Concepts

95IP Addresses in FINS Communications Section 5-2• Ethernet address: A fixed number is assigned to each EtherNet/IP Unit or built-in EtherNet/IP port

Page 27 - Overview of EtherNet/IP

96IP Addresses in FINS Communications Section 5-25-2-2 Pairing Addresses in Internal TablesFINS/UDP Communications MethodsAutomatic Generation (Dynami

Page 28 - 1-1 EtherNet/IP Unit Features

97IP Addresses in FINS Communications Section 5-2Automatic Generation (Static)With the static method as well, the following values are set for address

Page 29

98IP Addresses in FINS Communications Section 5-2ExampleCombined Method The combined method combines the IP address table method and the auto-matic ge

Page 30 - Switching Hubs

99IP Addresses in FINS Communications Section 5-2ExampleNote When an internal table IP address has been changed with the reception of aFINS command, t

Page 31

100IP Addresses in FINS Communications Section 5-2Note If the ETN11-compatible mode is used, the internal table will retain the samecontent from when

Page 32

101IP Addresses in FINS Communications Section 5-2 Local Device: FINS/TCP Server1,2,3... 1. A request to open a connection is received in TCP/IP prot

Page 33

102IP Addresses in FINS Communications Section 5-22. Set IP addresses for the devices to be connected.Set the IP address for the remote EtherNet/IP Un

Page 34 - Communications

103IP Addresses in FINS Communications Section 5-2server whenever the system is started. Therefore, at a personal computerusing the DHCP service, IP a

Page 35 - Controller Link

xiii W474 CJ2H-CPU6@-EIPCJ2H-CPU6@CJ2M-CPU@@CS1G/H-CPU-@@HCS1G/H-CPU-@@-V1CJ1G/H-CPU@@HCJ1M-CPU@@CJ1G-CPU@@NSJ@-@@@@(B)-G5DNSJ@-@@@@(B)-M3DProgrammabl

Page 36 - 1-5-1 Overview

104IP Addresses in FINS Communications Section 5-2Models Supporting Automatic Generation Method (Static)Models Supporting IP Address Table MethodProgr

Page 37

105IP Addresses in FINS Communications Section 5-2Models that Can Use the Combined Method5-2-5 Pairing IP Addresses and FINS Node AddressesThe followi

Page 38

106Private and Global Addresses Section 5-35-3 Private and Global Addresses5-3-1 Private and Global AddressesThere are two kinds of IP addresses, priv

Page 39 - Unit Specifications

107Private and Global Addresses Section 5-35-3-2 Using a Private Address for the EtherNet/IP UnitConditions for Using Communications ApplicationsWhen

Page 40 - Specifications

108Private and Global Addresses Section 5-3• With FINS/UDP, when the IP address (private address) of a computerserving as a DHCP client is changed, th

Page 41 - CJ-series EtherNet/IP Unit

109Private and Global Addresses Section 5-35-3-3 EtherNet/IP Unit with a Global AddressConditions for Using Communications ApplicationsCommunications

Page 42

110Private and Global Addresses Section 5-3• If the TCP port number (44818) or UDP port number (44818) that is usedfor EtherNet/IP cannot be used if p

Page 43

111SECTION 6Tag Data Link FunctionsThis section describes tag data link functions and related Network Configurator operations.6-1 Overview of Tag Data

Page 44

112Overview of Tag Data Links Section 6-16-1 Overview of Tag Data Links6-1-1 Tag Data LinksTag data links enable cyclic data exchanges on an EtherNet/

Page 45 - 2-1-4 Dimensions

113Overview of Tag Data Links Section 6-16-1-2 Overview of OperationSetting and Downloading Tag Data Link ParametersThe tag data link parameters (e.g.

Page 47 - 255.255.255.0

114Overview of Tag Data Links Section 6-1Another EtherNet/IP Unit must be mounted to the PLC to increase the maxi-mum number of connections. (Refer to

Page 48 - @@@@@@@@@@@@

115Overview of Tag Data Links Section 6-1If multicast connections are used, however, use a switching hub that has mul-ticast filtering, unless the tag

Page 49

116Overview of Tag Data Links Section 6-1System Configuration Conditions for Setting Tags Using Symbols or I/O Memory AddressesLocal tags for tag data

Page 50

117Overview of Tag Data Links Section 6-1There are both input and output tag sets. Each tag set can contain only inputtags or only output tags. The sa

Page 51 - Displays errors that occurred

118Overview of Tag Data Links Section 6-1Note The I/O memory words used in tags in a tag set do not have continuousaddresses. The tags can also be fro

Page 52 - 2-2-2 Switch Settings

119Overview of Tag Data Links Section 6-1To receive the PLC status, specify the PLC status in an input (consume) tag inthe reception tag set as well.

Page 53 - Node Address Setting

120Overview of Tag Data Links Section 6-1The following table shows the operation of each the bits when multiple con-nections are used to communicate w

Page 54 - 2-3-3 Switching Hub Types

121Setting Tag Data Links Section 6-26-2 Setting Tag Data Links6-2-1 Starting the Network ConfiguratorProcedure Tag data links are set by using the Ne

Page 55 - 2-3-4 Switching Hub Functions

122Setting Tag Data Links Section 6-2When the Network Configurator starts, the following window will be displayed. Main Window The Main Window consist

Page 56

123Setting Tag Data Links Section 6-2When two or more networks are being managed, a new Network Configura-tion Window can be added by selecting Networ

Page 57

xvRead and Understand this ManualPlease read and understand this manual before using the product. Please consult your OMRON representative if you have

Page 58

124Setting Tag Data Links Section 6-26-2-2 Tag Data Link Setting Procedure The section describes the procedure for setting tag data links (i.e., conne

Page 59 - SECTION 3

125Setting Tag Data Links Section 6-26-2-3 Registering DevicesRegister all of the devices required in the equipment (such as EtherNet/IPUnits performi

Page 60 - 3-1-1 Procedures

126Setting Tag Data Links Section 6-23. Set the IP address to match the node address (IP address) actually beingused in the device.4. Repeat steps 1 t

Page 61

127Setting Tag Data Links Section 6-22. Click the Tag Sets Tab at the top of the Edit Device Parameters Dialog Box.There are two kinds of tag sets: in

Page 62 - 3-2 Switch Settings

128Setting Tag Data Links Section 6-2Creating and Adding Tags 3. Click the Edit Tags Button. The Edit Tags Dialog Box will be displayed.Register the i

Page 63 - Setting the Node Address

129Setting Tag Data Links Section 6-2(b) Be sure to directly enter the CPU Unit's I/O memory address(e.g., 100, W100, D0) or a network symbol as

Page 64 - Mounting to a PLC Section 3-3

130Setting Tag Data Links Section 6-29. When you are finished registering the required tags, click the OK Button atthe bottom of the Edit Tags Dialog

Page 65 - 3-3-3 Mounting

131Setting Tag Data Links Section 6-2Changing and Registering Tag Sets11. The following dialog box will be displayed when the tags in the Edit TagsDia

Page 66 - 3-3-4 Handling Precautions

132Setting Tag Data Links Section 6-2Open the Edit Device Parameters Dialog Box, select the tag set containingthe tag that you want to delete, and cli

Page 67 - 3-4 Network Installation

133Setting Tag Data Links Section 6-213. In order to edit a registered tag set and add tags, either double-click the tagset, or select the tag set and

Page 68

xviApplication ConsiderationsSUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to

Page 69 - Cable Location

134Setting Tag Data Links Section 6-218. If you want to just add new tags and register the tag set, first register thetags with steps 1 to 9. In this

Page 70 - 3-5 Connecting to the Network

135Setting Tag Data Links Section 6-221. To register the newly added tags in a tag set, either double-click the de-sired tag set, or select the tag se

Page 71 - Example: CS1W-EIP21

136Setting Tag Data Links Section 6-22. Importing Network Symbols Created with the CX-Programmer to the Network ConfiguratorIf the CJ2H-CPU6@-EIP or C

Page 72 - 3-6 Creating I/O Tables

137Setting Tag Data Links Section 6-2A confirmation message will be displayed. Click the Yes Button. The symbols will be imported as shown below on th

Page 73 - Password

138Setting Tag Data Links Section 6-2To place more than one input symbol (input tag) imported from the CX-Programmer into one tag set, you must delete

Page 74

139Setting Tag Data Links Section 6-24. You can change tag set names in this dialog box. To confirm a change, clickthe OK Button in the dialog box. 5.

Page 75

140Setting Tag Data Links Section 6-2Importing the Tag and Tag Set CSV File with the CX-Programmer 1,2,3... 1. In the project global symbol table for

Page 76

141Setting Tag Data Links Section 6-26-2-5 Connection SettingsAfter creating the tag sets, click the Connections Tab at the top of the EditDevice Para

Page 77

142Setting Tag Data Links Section 6-23. In the Unregister Device List, select the target device that requires connec-tion settings by clicking the dev

Page 78 - 3-8 TCP/IP and Link Settings

143Setting Tag Data Links Section 6-21,2,3... 1. Select the Connection Tab and then click the New Button. The following Edit Connection Dialog Box wil

Page 79

xviiDisclaimersCHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons.It i

Page 80

144Setting Tag Data Links Section 6-2The settings are as follows:2. When the settings have been completed, press the Regist Button. Connections Settin

Page 81

145Setting Tag Data Links Section 6-2The following table describes the various settings in the dialog box.2. When the settings are completed, click th

Page 82

146Setting Tag Data Links Section 6-2Confirming the Connections Settings1,2,3... 1. An overview of the connections set in the Register Device List is

Page 83 - 3-9 Tag Data Link Parameters

147Setting Tag Data Links Section 6-24. If the tag set’s size is changed in either the originator or target after theconnection was set, the size will

Page 84

148Setting Tag Data Links Section 6-2Example 2: Automatic Connections with the EllipsesThe following connections would automatically be set if there i

Page 85

149Setting Tag Data Links Section 6-2Click the OK Button to start processing. 4. A device connection structure tree will be displayed when processing

Page 86

150Setting Tag Data Links Section 6-2•The Display the detail of Connection Check Box can be used to switchbetween device-level and connection-level di

Page 87 - 3-10 Other Parameters

151Setting Tag Data Links Section 6-2Node List The following items will be displayed in the Node Area on the left side of thewindow. • IP Address: The

Page 88 - Using FTP

152Setting Tag Data Links Section 6-2• Tag Set Name: If the Wizard is used, the names will be automaticallyassigned using consecutive IP addresses in

Page 89 - Using the Status Area

153Setting Tag Data Links Section 6-22. Select the memory area (here, W) in the Memory Field and enter the start-ing address (here, 0) and number of w

Page 91 - 3-11 Communications Test

154Setting Tag Data Links Section 6-2If the creating the data link table is continued, the data link table will be cre-ated with the same size of data

Page 92 - Application Example

155Setting Tag Data Links Section 6-2Automatic Allocation Results for Node 3 (IP Address: 192.168.250.3)6. After entering all of the settings in the

Page 93 - Memory Allocations

156Setting Tag Data Links Section 6-2b. No Table Inconsistencies The following message will be displayed. Click the OK Button. 7. Select Exit from the

Page 94

157Setting Tag Data Links Section 6-2The following dialog box will be displayed before the Wizard starts. Click the Yes Button to delete the connectio

Page 95

158Setting Tag Data Links Section 6-2The following display will appear when you click the Show Detail Button. The specified values for detailed parame

Page 96 - 4-2 CIO Area Allocations

159Setting Tag Data Links Section 6-26-2-8 Creating Connections by Device Dragging and Dropping You can create a connection to the originator by dragg

Page 97 - User Settings

160Setting Tag Data Links Section 6-2• If there is no applicable input tag set at the originator, you can createa new one by using the Edit Tag Sets B

Page 98

161Setting Tag Data Links Section 6-2Note The following dialog box will be displayed if a target device that does not haveI/O data is dropped. Before

Page 99

162Setting Tag Data Links Section 6-2The Network Configurator will connect to the EtherNet/IP network. If theNetwork Configurator is connected online

Page 100

163Setting Tag Data Links Section 6-23. Input the EtherNet/IP Unit’s unit number in the Unit No. Field, select theconnecting COM port number, and clic

Page 101 - CPU Unit) (n + 11)

xixUnit Versions of CS/CJ-seriesUnit Versions A “unit version” has been introduced to manage Units in the CS/CJ Seriesaccording to differences in func

Page 102

164Setting Tag Data Links Section 6-22. Select Network - Connect. The Setup Interface Dialog Box will be dis-played.3. Set the port type to either USB

Page 103

165Setting Tag Data Links Section 6-27. Select the port for the EtherNet/IP Unit and then click the OK Button. TheNetwork Configurator will be connect

Page 104

166Setting Tag Data Links Section 6-22. Select Network - Connect. The following Setup Interface Dialog Box will be displayed. 3. Click the Setup Butto

Page 105 - Configuration set

167Setting Tag Data Links Section 6-2• Node addressLast value in the IP address of the Unit above (e.g., 3 for192.168.251.3)• Unit number of CPU Bus U

Page 106

168Setting Tag Data Links Section 6-2is clicked in the dialog box above. (Refer to the following figure.)6-2-10 Downloading Tag Data Link ParametersTo

Page 107

169Setting Tag Data Links Section 6-21,2,3... 1. Connect the Network Configurator online.2. There are two ways to download the parameters.• Downloadin

Page 108

170Setting Tag Data Links Section 6-2If the Download after changed to Program mode Button is clicked, allCPU Units will be changed to PROGRAM mode and

Page 109 - 4-3 DM Area Allocations

171Setting Tag Data Links Section 6-2If the operating mode of one or more CPU Units was changed to downloadthe parameters, the CPU Units can be return

Page 110

172Setting Tag Data Links Section 6-2Select the icon of the EtherNet/IP Unit from which you want to upload. Toselect multiple nodes, press and hold th

Page 111 - 4-4 User Settings Area

173Setting Tag Data Links Section 6-2Verifying the Network ConfigurationCompare the list of registered devices in the Network Configuration Windowwith

Page 113

xxNote The unit version will be displayed in the Unit Manufacturing Information DialogBox.Using Unit Version Label The following unit version label is

Page 114 - 4-5 Auxiliary Area Data

174Setting Tag Data Links Section 6-2Click the OK Button or the Close Button. Verifying the Device ParametersUse the following procedure to compare th

Page 115

175Setting Tag Data Links Section 6-2• Differences Found in the Device Type Click the OK Button or the Close Button.5. If multiple nodes have been sel

Page 116

176Setting Tag Data Links Section 6-2Start Connection Button:Starts all connections for which the device is the originator. Stop Connection Button:Sto

Page 117 - Determining IP Addresses

177Setting Tag Data Links Section 6-23. Select Device - Reset. The following dialog box will be displayed.• Clicking the Yes Button:The following dial

Page 118 - 5-1 IP Addresses

178Setting Tag Data Links Section 6-2The network configuration file save operation is complete.3. When the network configuration is changed later, the

Page 119 - 5-1-4 Subnet Masks

179Setting Tag Data Links Section 6-21,2,3... 1. Select File - Open or click the Button. The following dialog box willbe displayed.If the network co

Page 120 - 5-1-5 CIDR

180Setting Tag Data Links Section 6-25. Select any of the options as necessary. The options are listed below. Note The save format will vary depending

Page 121

181Setting Tag Data Links Section 6-26-2-18 Changing DevicesDevices that are registered in a network configuration with the Network Con-figurator can

Page 122 - TCP port

182Setting Tag Data Links Section 6-2Icon Status (gray)Offline Default (no configuration)(turquoise edge) (green)Idle (CPU Unit of PLC is in PROGRAM m

Page 123 - Remote FINS node number

183Ladder Programming with Tag Data Links Section 6-36-3 Ladder Programming with Tag Data Links6-3-1 Ladder Programming Related to Tag Data LinksIf da

Page 124

xxiPRECAUTIONSThis section provides general precautions for using the CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports.The information co

Page 125

184Ladder Programming with Tag Data Links Section 6-3Programming for Revision 2 or HigherProgramming for Revision 1 and Revision 2Programming to Detec

Page 126

185Ladder Programming with Tag Data Links Section 6-3Programming for Revision 1 or HigherExample of Programming to Process DataThe following type of p

Page 127 - FINS node number transmission

186Ladder Programming with Tag Data Links Section 6-3Note Even if an error occurs in communications with a target device, the input datafrom the targe

Page 128 - 5-2-3 Application Examples

187SECTION 7Message Communications FunctionsThis section describes message communications using FINS messages and explicit messages.7-1 Overview . . .

Page 129

188Overview Section 7-17-1 OverviewThe message communications functions send command/response messagesbetween nodes on the Ethernet network. The messa

Page 130 - Address Table Method

189Overview Section 7-1Overall StructureNote With the EtherNet/IP Unit or built-in EtherNet/IP port, message communica-tions are possible even if the

Page 131 - FINS/UDP and FINS/TCP

190FINS Message Communications Section 7-27-2 FINS Message CommunicationsMessages containing FINS commands can be exchanged over the Ethernetnetwork b

Page 132 - (required)

191FINS Message Communications Section 7-2Note FINS commands sent and received by the CS/CJ-series EtherNet/IPUnit include commands addressed to the C

Page 133 - ■ FINS Communications Service

192Explicit Message Communications Section 7-37-3 Explicit Message CommunicationsExplicit messages defined in EtherNet/IP can be used to send servicer

Page 134

193Message Communications Specifications Section 7-47-4 Message Communications SpecificationsCPU Unit function CS/CJ SeriesUnit model number CS1W-EIP2

Page 135

xxiiIntended Audience 11 Intended AudienceThis manual is intended for the following personnel, who must also haveknowledge of electrical systems (an e

Page 136

194Message Communications Error Indications Section 7-57-5 Message Communications Error IndicationsThere are two ways to obtain information on communi

Page 137 - Tag Data Link Functions

195Message Communications Errors Section 7-67-6 Message Communications ErrorsThe following table shows the main errors that may occur when messages ar

Page 138 - 6-1-1 Tag Data Links

196Message Communications Errors Section 7-6

Page 139 - 6-1-2 Overview of Operation

197SECTION 8FINS CommunicationsThis section provides information on communicating on EtherNet/IP Systems and interconnected networks using FINScommand

Page 140

198Overview of FINS Communications Section 8-18-1 Overview of FINS Communications8-1-1 Communications On an Ethernet NetworkThe EtherNet/IP Units and

Page 141

199Overview of FINS Communications Section 8-18-1-2 Using the FINS/UDP and FINS/TCP MethodsIt is recommended that FINS/UDP and FINS/TCP be used as fol

Page 142 - 6-1-4 Data Link Data Areas

200FINS/UDP Method Section 8-28-2 FINS/UDP Method8-2-1 OverviewFINS/UDP Features The FINS/UDP method is a FINS communications method that uses the UDP

Page 143 - PLC status

201FINS/UDP Method Section 8-2UDP Port Numbers for FINS/UDPThe UDP port number is the number for UDP to identify the application layer(i.e., the FINS

Page 144 - PLC Error Flag

202FINS/TCP Method Section 8-38-3 FINS/TCP Method8-3-1 OverviewFINS/TCP FeaturesThe FINS/TCP method is a FINS communications method that uses the TCP/

Page 145 - Connection

203FINS/TCP Method Section 8-3• After a FINS/TCP connection (connection number, remote IP address)has been set in the FINS/TCP Tab Page of the Network

Page 146

xxiiiSafety Precautions 3!WARNING Provide safety measures in external circuits (i.e., not in the ProgrammableController), including the following item

Page 147 - 6-2 Setting Tag Data Links

204FINS/TCP Method Section 8-3FINS/TCP Connection Status (Word n+24)While a connection with a remote node is established, the bit corresponding tothe

Page 148

205FINS/TCP Method Section 8-3After a connection has been established as a FINS/TCP client, it can be termi-nated in the following ways.• If the conne

Page 149

206FINS/TCP Method Section 8-3• When routing tables are used for one or more other nodes on the samenetworkIt is not necessary to set routing tables i

Page 150

207Routing Tables Section 8-48-4 Routing TablesWhen the FINS communications service is used, routing tables must be cre-ated in advance. Routing tabl

Page 151 - 6-2-3 Registering Devices

208Routing Tables Section 8-4The following example shows routing tables for sending data from PLC #1 (thelocal node: network address 1, node address 1

Page 152

209Routing Tables Section 8-48-4-3 Routing Table Setting Examples Example 1: Local Network Table for a PLC With Multiple Units MountedThis example sh

Page 153

210Routing Tables Section 8-4 Example 3: All NodesThis example uses the following configuration to show the routing tables for allnodes. PLC5PLC1EIP

Page 154

211Using FINS Applications Section 8-58-5 Using FINS Applications8-5-1 CX-Programmer (CX-Server)The following examples show how to connect online from

Page 155 - Select Disable or Enable

212Using FINS Applications Section 8-5Example: Inputs to the CX-Programmer's Setup WindowExample: Change PLC Settings Example: Network Settings (

Page 156

213Using FINS Applications Section 8-5Example: Network Settings (Driver Tab Page) System Configuration Example 2: Using Routing TablesIn this examp

Page 157

xxivOperating Environment Precautions 44 Operating Environment Precautions!Caution Do not operate the control system in the following locations:• Loca

Page 158

214Using FINS Applications Section 8-5CX-Programmer's FINS/UDP Tab Page in Edit Parameters Dialog BoxSame as for System Configuration Example 1.R

Page 159

215Using FINS Applications Section 8-58-5-2 FinsGateway FinsGateway Ver. 2003 must be used to communicate using FINS/TCPbetween applications serving a

Page 160

216Using FINS Applications Section 8-5• Communication Unit Tab Page• UDP Nodes Tab Page: Automatic Generation Method (Dynamic or Passive)• UDP port nu

Page 161

217Using FINS Applications Section 8-5 • UDP Nodes Tab Page: IP Address Table Method or Combined MethodClick the Add Button, and then set the IP addre

Page 162 - Configurator

218Using FINS Applications Section 8-5• TCP Nodes Tab PageClick the Add Button, and then set the IP address table in the following Ether-net Node Defi

Page 163

219Using FINS Applications Section 8-5 System Configuration Example 3: Connecting the CX-Programmer Online Using the FINS/TCP MethodIn this example,

Page 164

220Communicating between OMRON PLCs Section 8-68-6 Communicating between OMRON PLCsFINS commands can be sent from the CPU Unit of a PLC by using theSE

Page 165

221Communicating between OMRON PLCs Section 8-68-6-2 PLC Communications Data AreasThe following table shows the I/O data areas involved when SEND(090)

Page 166

222Communicating between OMRON PLCs Section 8-68-6-3 Using SEND(090), RECV(098), and CMND(490)Make the settings shown below when using the SEND(090),

Page 167 - 6-2-5 Connection Settings

223Communicating between OMRON PLCs Section 8-6RECV(098) With the RECV(098) instruction, the data in m number of words, starting fromthe beginning wor

Page 168

xxvApplication Precautions 5• Always use the power supply voltages specified in the operation manuals.An incorrect voltage may result in malfunction o

Page 169

224Communicating between OMRON PLCs Section 8-6CMND(490) The CMND(490) instruction sends n bytes of command data, starting from thebeginning word S at

Page 170

225Communicating between OMRON PLCs Section 8-6Commands Addressed to CS/CJ-series CPU UnitsThe following table provides a list of FINS commands that c

Page 171

226Communicating between OMRON PLCs Section 8-68-6-4 Writing ProgramsPrograms incorporating the SEND(090), RECV(098), and CMND(490)instructions are ge

Page 172

227Communicating between OMRON PLCs Section 8-6 The execution status of the SEND(090), RECV(098), and CMND(490) instruc-tions is always reflected by t

Page 173 - Connections

228Communicating between OMRON PLCs Section 8-6Communications Port Completion CodesThe status of a SEND(090), RECV(098), and CMND(490) instruction aft

Page 174

229Communicating between OMRON PLCs Section 8-6 10100000 0000 0000ExampleCommunications Port Enabled FlagCommunications instruction:SEND(090), RECV(09

Page 175 - Structure Tree

230Communicating between OMRON PLCs Section 8-68-6-5 Program ExampleWhen the Communications Port Enabled Flag for port 7 is ON, and RECV(098) is not b

Page 176

231Communicating between OMRON PLCs Section 8-6Note 1. With CS/CJ-series PLCs, the Communications Port Enabled Flags at bits0 to 7 in word A202 turn O

Page 177

232Precautions on High Traffic in FINS Communications Section 8-78-7 Precautions on High Traffic in FINS CommunicationsWhen applications are construct

Page 178 - ■ Allocations

233SECTION 9Message CommunicationsThis section describes message communications using FINS commands sent from the ladder program in the CPU Unit ofthe

Page 179

xxviConformance to EC Directives 6• When transporting the Unit, use special packing boxes and protect it frombeing exposed to excessive vibration or i

Page 180

234Sending Explicit Messages Section 9-19-1 Sending Explicit MessagesCS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports can sendexplicit me

Page 181

235Sending Explicit Messages Section 9-1in the same network layer and the remote node’s IP address range is lim-ited.The following diagram shows an ex

Page 182

236Sending Explicit Messages Section 9-1CIP UCMM MESSAGE SEND (28 10)This command sends an explicit message for CIP routing to another node’sspecified

Page 183

237Sending Explicit Messages Section 9-1Response BlockThe following normal response is returned to a transmitted CIP UCMM MES-SAGE SEND command if it

Page 184

238Sending Explicit Messages Section 9-1In the routing format for rely hops, the first service code (in the routing servicedata) is 52 Hex, which is t

Page 185 - Drag & Drop

239Sending Explicit Messages Section 9-1This hexadecimal value is returned to indicate the number of words of data inthe additional status field.Addit

Page 186

240Sending Explicit Messages Section 9-1Ann Arbor, Michigan 48108-5006USATEL: 1 734-975-8840FAX: 1 734-922-0027Email [email protected] www.odva.org

Page 187 - Ethernet

241Sending Explicit Messages Section 9-1EXPLICIT MESSAGE SEND (28 01)EXPLICIT MESSAGE SEND will send a DeviceNet Unit-compatible explicitmessage to th

Page 188 - Network connection icon

242Sending Explicit Messages Section 9-1Class ID (command):The class ID of the destination of the explicit message.Instance ID (command):The instance

Page 189

243Sending Explicit Messages Section 9-19-1-1 Sending Explicit Messages Using CMND(490)With a CS/CJ-series EtherNet/IP Unit or built-in EtherNet/IP po

Page 190

1SECTION 1Overview of EtherNet/IP This section introduces the functions and protocols used in EtherNet/IP Unit or built-in EtherNet/IP port communicat

Page 191 - EtherNet/IP

244Sending Explicit Messages Section 9-1Setting the Command Data for CMND(490)The response data is set in the same way, starting from the word specifi

Page 192

245Sending Explicit Messages Section 9-1data and ERROR CLEAR codes, is also returned in the same order from lowto high bytes in the response block.Exa

Page 193

246Sending Explicit Messages Section 9-1D01016 = 382E hex IP address: “8.”D01017 = 3235 hex IP address: “25”D01018 = 302E hex IP address: “0.”D01019 =

Page 194

247Sending Explicit Messages Section 9-1Program ExampleSets 0000 in D00000 to D02999.Shifts the contents of CIO 0000 one bit to the right and retries

Page 195

248Receiving Explicit Messages Section 9-29-2 Receiving Explicit MessagesThe CS/CJ-series EtherNet/IP Units and built-in EtherNet/IP ports areequipped

Page 196

249Receiving Explicit Messages Section 9-29-2-1 List of PLC Object ServicesPLC Objects provide the following services.Status Read/Write for CPU UnitsS

Page 197

250Receiving Explicit Messages Section 9-2I/O Memory Read/Write for CPU UnitsNote With a EtherNet/IP Unit or built-in EtherNet/IP port with unit versi

Page 198

251Receiving Explicit Messages Section 9-2CPU Information Read (Service Code: 0E Hex)Reads CPU Unit information, including operating mode, fatal/non-f

Page 199 - Configuration

252Receiving Explicit Messages Section 9-2Note The codes for the above modes are 1-word (2-byte) data and are returned inlow byte first. For example,

Page 200 - Parameters

253Receiving Explicit Messages Section 9-2• CPU Operating Mode (Attribute ID = 64 Hex)Changes the CPU Unit operating mode.The Attribute Values are as

Page 201

2EtherNet/IP Unit Features Section 1-11-1 EtherNet/IP Unit FeaturesEtherNet/IP is an industrial multi-vendor network that uses Ethernet compo-nents. T

Page 202

254Receiving Explicit Messages Section 9-2CPU Unit Status Read (Service Code: 40 Hex)This PLC Object service reads status details (operation status, o

Page 203

255Receiving Explicit Messages Section 9-2• Operating mode: Returns the operating mode of the CPU Unit in 1-byte(2-digit) hexadecimal.0001 Hex: PROGRA

Page 204

256Receiving Explicit Messages Section 9-2• Message Exists/Does Not Exist: When the MSG instruction is executedby the CPU Unit, the bit corresponding

Page 205

257Receiving Explicit Messages Section 9-2Class ID (command): Always C4 (2F).The class ID depends on the unit version. The class ID is C4 for unit ver

Page 206 - 6-2-17 Checking Connections

258Receiving Explicit Messages Section 9-2Response BlockParameters Service code (command, response): ID Hex is specified for commands. Forresponses, t

Page 207 - 6-2-18 Changing Devices

259Receiving Explicit Messages Section 9-2Command BlockNote A body format of either 8 bits or 16 bits is possible.Response BlockParameters Service cod

Page 208

260Receiving Explicit Messages Section 9-2Command BlockNote A body format of either 8 bits or 16 bits is possible.Response BlockParameters Service cod

Page 209

261SECTION 10Communications Performance and Communications LoadThis section describes the communications performance in an EtherNet/IP network, and sh

Page 210 - Operating

262Communications System Section 10-110-1 Communications System10-1-1 Tag Data Link Communications MethodPacket Interval (RPI) SettingsIn EtherNet/IP

Page 211

263Communications System Section 10-1Packet Interval (RPI) and Bandwidth Usage (PPS)In a tag data link, the number of packets transferred each second

Page 212

3EtherNet/IP Unit Features Section 1-1FTP Server A built-in FTP server is provided to enable transferring files in the PLC to andfrom a host computer.

Page 213 - SECTION 7

264Communications System Section 10-110-1-2 Calculating the Number of Connections The maximum number of connections for the Unit is 32 for the CJ2M an

Page 214 - Overview Section 7-1

265Communications System Section 10-110-1-3 Network Transmission Delay TimeIn an EtherNet/IP network, the tag data link packets are sent once eachpack

Page 215

266Communications System Section 10-13. Switching Hub DelayThe switching hub delay is the delay time between the arrival of the packet atthe switching

Page 216

267Communications System Section 10-1PLC #1 PLC #2 PLC #3 PLC #17#17 #3 #2 200 words 200 words 200 words× 165 ms5 ms200 words 5 ms

Page 217 - Ethernet (EtherNet/IP)

268Adjusting the Communications Load Section 10-210-2 Adjusting the Communications Load In an Ethernet network using a switching hub, the network band

Page 218

269Adjusting the Communications Load Section 10-210-2-1 Checking Bandwidth Usage for Tag Data LinksThe Network Configurator can display the bandwidth

Page 219

270Adjusting the Communications Load Section 10-2Checking the Usage of Capacity and Network Bandwidth for Tag Data LinksThe percentage of the allowabl

Page 220 - Not relevant

271Adjusting the Communications Load Section 10-2Example:If the RPI is set to 50 ms for all connections and the usage of capacity is40%, the usage of

Page 221

272Adjusting the Communications Load Section 10-2• Is the network bandwidth usage without multicast filtering under 100Mbps for each node or the usage

Page 222

273Adjusting the Communications Load Section 10-2The Usage of Capacity column will show the percentage of the allowed tagdata link bandwidth being use

Page 223 - FINS Communications

CS1W-EIP21 (100Base-TX)CJ1W-EIP21 (100Base-TX)CJ2H-CPU6@-EIP (100Base-TX)CJ2M-CPU3@ (100Base-TX/10Base-T)EtherNet/IP UnitsOperation ManualRevised Febr

Page 224 - Physical Layer

4Devices Required for Constructing a Network Section 1-21-2 Devices Required for Constructing a NetworkThe basic configuration for an EtherNet/IP Syst

Page 225

274Adjusting the Communications Load Section 10-2Method 2: Changing a Particular Device’s RPI SettingThe usage of capacity can be adjusted for only a

Page 226 - 8-2 FINS/UDP Method

275Adjusting the Communications Load Section 10-2a. Click the Close Button at the bottom of the Usage of Device BandwidthDialog Box.b. Double-click th

Page 227 - FINS/UDP Method Section 8-2

276Adjusting the Communications Load Section 10-24. If the usage of capacity cannot be adjusted to the desired level when thesetting described above h

Page 228 - 8-3 FINS/TCP Method

277Adjusting the Communications Load Section 10-2Example ConditionsConnectionsIn this example, there are 10 CS1W-EIP21 Units and 10 CJ1W-EIP21 Unitsfo

Page 229 - FINS/TCP Method Section 8-3

278Adjusting the Communications Load Section 10-2Changing the SettingsMethod 1: Same Packet Interval Setting for All ConnectionsThe percentage of the

Page 230

279Adjusting the Communications Load Section 10-2If the packet interval for all connections has been set to the same setting, thedialog box will show

Page 231

280Adjusting the Communications Load Section 10-2The Usage of Capacity values also indicate that the Usage of Capacity hasincreased (from 39.67% to 43

Page 232

281Adjusting the Communications Load Section 10-2Method 3: Changing the Packet Interval (RPI) of Only Specific Connections In this example, we want a

Page 233 - 8-4-1 Routing Table Overview

282Adjusting the Communications Load Section 10-2In the Edit Connection Dialog Box, input 1.0 ms as the new RPI value, andclick the OK Button. The tag

Page 234 - Routing Tables Section 8-4

283I/O Response Time in Tag Data Links Section 10-310-3 I/O Response Time in Tag Data LinksNote This section describes the data processing time for an

Page 235

5Support Software Required to Construct a Network Section 1-3 Refer to the CX-Programmer Operation Manual (Cat. No. W446) for informa-tion on the CX-P

Page 236

284I/O Response Time in Tag Data Links Section 10-3The maximum number of tag data link words that can be transferred by oneEtherNet/IP Unit or CJ2H bu

Page 237 - 8-5 Using FINS Applications

285I/O Response Time in Tag Data Links Section 10-3Note (1) When one of the listed CPU Bus Units is mounted in a CS-series Long-distance Rack, the I/O

Page 238

286I/O Response Time in Tag Data Links Section 10-3The following table gives the items required to find the I/O response time andvalues used in calcul

Page 239 - 1 (EtherNet/IP Unit)

287I/O Response Time in Tag Data Links Section 10-3(1) Node 1 (PLC #1) Input ON Response TimeThis is the delay time for the external input device from

Page 240

288I/O Response Time in Tag Data Links Section 10-3(3) Packet Interval (RPI)This is the communications refresh cycle set for each connection using the

Page 241 - 8-5-2 FinsGateway

289I/O Response Time in Tag Data Links Section 10-3(6) Output ON response timeThis is the delay time for the external output device from when the outp

Page 242 - • Communication Unit Tab Page

290I/O Response Time in Tag Data Links Section 10-3Minimum Tag Data Link I/O Response TimeThe minimum tag data link I/O response time, which occurs wh

Page 243

291Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports Section 10-410-4 Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports10-4-1

Page 244

292Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports Section 10-4If the same RPI is set for all connections, 12 ms is the lowest setting t

Page 245

293Tag Data Link Performance for CJ2M Built-in EtherNet/IP Ports Section 10-4For example, the maximum and minimum I/O response times would be as fol-l

Page 246

6Communications Services Overview Section 1-4Refer to the CX-Integrator Operation Manual (Cat. No. W464) for informationon the CX-Integrator. 1-4 Comm

Page 247

294Message Service Transmission Delay Section 10-510-5 Message Service Transmission DelayThis section explains the maximum transmission delay that can

Page 248 - (@)SEND(90)

295Message Service Transmission Delay Section 10-5For details, refer to the CPU Unit’s Operation Manual.CPU Bus Unit Service Processing Time (Local No

Page 249 - (@)RECV(98)

296Message Service Transmission Delay Section 10-5CPU Bus Unit Service Processing Time (Remote Node)The following table shows the CPU Bus Unit service

Page 250 - (@)CMND(490)

297Message Service Transmission Delay Section 10-5RECV(098) InstructionMaximum transmission delay =CPU Bus Unit service cycle (Local node, 1)+ CPU Bus

Page 251

298Message Service Transmission Delay Section 10-5For details, refer to the CPU Unit’s Operation Manual.Send ProcessingTransmission Delay The transmis

Page 252 - 8-6-4 Writing Programs

299Message Service Transmission Delay Section 10-5Note CJ2 CPU Units support only Normal Mode.For details, refer to the CPU Unit’s Operation Manual.CP

Page 253

300Message Service Transmission Delay Section 10-5Example Calculation In this example, RECV(098) is used to receive 256 words of data from anotherPLC.

Page 254

301SECTION 11FTP ServerThis section describes the functions provided by the FTP server.11-1 Overview and Specifications. . . . . . . . . . . . . . . .

Page 255

302Overview and Specifications Section 11-111-1 Overview and Specifications11-1-1 OverviewThe EtherNet/IP Unit or built-in EtherNet/IP port has a buil

Page 256 - 8-6-5 Program Example

303FTP Server Function Details Section 11-211-1-2 SpecificationsNote The PLC, however, is unable to read or write files at other nodes using FTPbecaus

Page 257 - (See note 1.)

7Communications Services Overview Section 1-4Note In this example, a connection is established with the originator’s tag list con-taining tags a to g

Page 258 - ■ Conditions for High Traffic

304FTP Server Function Details Section 11-211-2-2 Connecting to the FTP ServerThe host computer must connect to the FTP server before the FTP serverfu

Page 259 - Message Communications

305Using the FTP Server Function Section 11-311-3 Using the FTP Server Function11-3-1 Procedure1,2,3... 1. Make the basic settings. Refer to Initial S

Page 260 - Explicit message

306Using the FTP Server Function Section 11-311-3-3 FTP TabThe CPU Bus Unit System Setup, which is set when using the FTP serverfunction, is shown in

Page 261 - PLC's

307FTP Server Application Example Section 11-411-4 FTP Server Application ExampleThe following procedure shows how to use the FTP server by connection

Page 262 - CIP UCMM MESSAGE SEND (28 10)

308Using FTP Commands Section 11-511-5 Using FTP CommandsThis section describes the FTP commands which the host computer (FTP cli-ent) can send to the

Page 263 - (See note.)

309Using FTP Commands Section 11-5userFormatuser [user_name]FunctionSpecifies the user name. Specify the FTP login name set in the EtherNet/IPUnit or

Page 264

310Using FTP Commands Section 11-5mkdirFormatmkdir DIRECTORY_NAMEFunctionCreates a directory of the specified name at the remote host (Memory Card orE

Page 265

311Using FTP Commands Section 11-5typeFormattype data_typeFunctionSpecifies the file data type. The following data types are supported:ascii: Files a

Page 266

312Using FTP Commands Section 11-5Any existing file with the same name in the remote host (Memory Card or EMFile Memory) will be overwritten by the co

Page 267 - EXPLICIT MESSAGE SEND (28 01)

313Using FTP Commands Section 11-511-5-3 Error Messages and FTP StatusError Messages The error messages returned by the EtherNet/IP Unit or built-in E

Page 268

8Communications Services Overview Section 1-4FINS Communications ServiceFINS commands can be sent to or received from other PLCs or computers onthe sa

Page 269

314Checking FTP Status Section 11-6PPP: Path nameXXX: IP addressYY: Port numberMM: FINS error codeNN: Socket error code11-6 Checking FTP Status11-6-1

Page 270 - Message request size

315Using File Memory Section 11-711-7 Using File MemoryThere are two media that can be used to store files in memory for CS/CJ-series PLCs: • Memory C

Page 271

316Using File Memory Section 11-7File Names Handled by CPU UnitThe files described in the following table can be read or written by the CPUUnit.Note 1

Page 272

317Using File Memory Section 11-711-7-3 Initializing File Memory11-7-4 I/O Memory Data Format IOM FormatThe IOM format is a data format used for bina

Page 273 - Program Example

318Using File Memory Section 11-7Example: Data format using words delimited by tabs and CRs after every10 fields. CSV FormatThe CSV format is a data

Page 274

319Using File Memory Section 11-7Example: Data format using words delimited by commas with CRs after every10 fields.Note FREAD(700) will not be able t

Page 275

320FTP File Transfer Time Section 11-811-8 FTP File Transfer TimeFile transfers using FTP can require 30 or 40 minutes depending on thecapacity of the

Page 276

321Host Computer Application Example Section 11-911-9 Host Computer Application ExampleThe following procedure provides an example of FTP operations f

Page 277 - Attribute Value

322Host Computer Application Example Section 11-94. Change to the MEMCARD directory.5. Change data type to binary.6. Transfer the file RESULT.IOM to t

Page 278

323SECTION 12Automatic Clock Adjustment FunctionThis section provides an overview of the automatic clock adjustment function, including details on spe

Page 279

9Communications Services Overview Section 1-4The FINS gateway function enables access to PLCs on not only the sameEthernet network but on various othe

Page 280 - Detailed status

324Automatic Clock Adjustment Section 12-112-1 Automatic Clock Adjustment12-1-1 OverviewThe EtherNet/IP Unit or built-in EtherNet/IP port can obtain t

Page 281

325Using the Automatic Clock Adjustment Function Section 12-212-1-2 Specifications12-2 Using the Automatic Clock Adjustment Function 12-2-1 Procedure1

Page 282 - Address H

326Using the Automatic Clock Adjustment Function Section 12-212-2-2 Settings Required for Automatic Clock Adjustment FunctionThe following settings mu

Page 283 - No. of words read

327Using the Automatic Clock Adjustment Function Section 12-212-2-3 Auto Adjust TimeThe contents in the CPU Bus Unit System Setup that are set for usi

Page 284

328Automatic Clock Adjustment Switch Section 12-312-3 Automatic Clock Adjustment SwitchThe Automatic Clock Adjustment Switch is allocated in the CIO A

Page 285

329Automatic Clock Adjustment Error Processing Section 12-4The error log can be read by sending FINS commands to the EtherNet/IP Unitor built-in Ether

Page 286

330Automatic Clock Adjustment Error Processing Section 12-4Note (1) For details on other error log information, refer to the Operation Manual,Construc

Page 287 - SECTION 10

331SECTION 13Maintenance and Unit ReplacementThis section describes cleaning, inspection, and Unit replacement procedures, as well as the Simple Backu

Page 288 - 10-1 Communications System

332Maintenance and Replacement Section 13-113-1 Maintenance and ReplacementThis section describes the routine cleaning and inspection recommended asre

Page 289 - Packet Interval (RPI)

333Simple Backup Function Section 13-2• If there is a faulty contact, try wiping the contact with a clean, lint-freecloth dampened with alcohol.Note T

Page 290 - Multicast

10Network Configurator Overview Section 1-51-5 Network Configurator Overview1-5-1 OverviewThe Network Configurator Ver. 3.0 or higher is a software pa

Page 291 - 1. Send Processing

334Simple Backup Function Section 13-2Applications Use the simple backup function when creating a backup data file for the entirePLC (including the CP

Page 292

335Simple Backup Function Section 13-2This operation will create an EtherNet/IP Unit or built-in EtherNet/IP port set-tings file, and write that file

Page 293

336Using the Backup Tool Section 13-3Comparing EtherNet/IP Unit or Built-in EtherNet/IP Port Data with the Setup File in the Memory CardSet pins 7 and

Page 294

337Using the Backup Tool Section 13-3Usage The PLC Backup Tool can be used for the following:• Backing up all data in a PLC• Comparing all of the data

Page 295

338Using the Backup Tool Section 13-3

Page 296

339SECTION 14Troubleshooting and Error ProcessingThis section describes error processing, periodic maintenance operations, and troubleshooting procedu

Page 297

340Checking Status with the Network Configurator Section 14-114-1 Checking Status with the Network Configurator14-1-1 The Network Configurator’s Devic

Page 298 - 10-2-4 Changing the RPI

341Checking Status with the Network Configurator Section 14-1Status 2 Tab Page The Status 2 Tab Page’s Target PLC Status Field shows the status of the

Page 299

342Checking Status with the Network Configurator Section 14-1Note The target PLC status is can be used when the PLC status is selected for allthe targ

Page 300

343Checking Status with the Network Configurator Section 14-1Connection Tab Page The Connection Tab Page’s Target Node Status Field shows the connecti

Page 301

11Network Configurator Overview Section 1-51-5-3 Precautions When Using the Network ConfiguratorOnly an OMRON EtherNet/IP Unit can be set as the origi

Page 302 - 10-2-5 RPI Setting Examples

344Checking Status with the Network Configurator Section 14-1Error History Tab Page The Error History Tab Page displays the error log stored in the Et

Page 303 - Bandwidth Usage

345Checking Status with the Network Configurator Section 14-1Refer to the operation manual of the CPU Unit for details on error information. Tag Statu

Page 304 - Settings

346Checking Status with the Network Configurator Section 14-1If the status is not “OK,” check the tag data link settings or the network symbolsettings

Page 305

347Using the LED Indicators and Display for Troubleshooting Section 14-2Ethernet Information Tab PageThe Ethernet Information Tab Page shows the commu

Page 306

348Using the LED Indicators and Display for Troubleshooting Section 14-2Lit red Not lit H3 EtherNet/IP Unit or built-in EtherNet/IP port faulty--- Ope

Page 307

349Using the LED Indicators and Display for Troubleshooting Section 14-2Flashing red--- HA CPU Unit memory errorA parity error occurred during an oper

Page 308

350Using the LED Indicators and Display for Troubleshooting Section 14-2Flashing red--- HE CPU Unit ser-vice monitor-ing errorServicing from the CPU U

Page 309

351Using the LED Indicators and Display for Troubleshooting Section 14-2Errors Related to the CPU UnitThe 7-segment display alternates between the nod

Page 310

352Using the LED Indicators and Display for Troubleshooting Section 14-2Errors Related to the Tag Data LinksThe 7-segment display alternates between t

Page 311 - Coefficient

353Using the LED Indicators and Display for Troubleshooting Section 14-2Errors Related to Memory AccessThe 7-segment display alternates between the no

Page 312

12Network Configurator Overview Section 1-5

Page 313 - : Data exchange

354Using the LED Indicators and Display for Troubleshooting Section 14-2Flashing red--- E8 Device Param-eters ErrorThe I/O Area set in the device para

Page 314

355Using the LED Indicators and Display for Troubleshooting Section 14-2Errors Related to the NetworkThe 7-segment display alternates between the node

Page 315

356Using the LED Indicators and Display for Troubleshooting Section 14-2--- --- E3 Server Con-nection ErrorAn error occurred in communica-tions with t

Page 316

357Using the LED Indicators and Display for Troubleshooting Section 14-2--- --- E3 Server Con-nection ErrorAn error occurred in transmission to the SN

Page 317 - 10-4-1 Overview

358Connection Status Codes and Error Processing Section 14-3Errors Related to the Unit The 7-segment display alternates between the node address and e

Page 318

359Connection Status Codes and Error Processing Section 14-3Email [email protected] www.odva.org The following table shows the possible originator/targ

Page 319

360Connection Status Codes and Error Processing Section 14-301 0109 Error code returned from target:The connection size settings are different in the

Page 320 - SEND(090) Instruction

361Connection Status Codes and Error Processing Section 14-301 011A Error code returned from origi-nator:Connection could not be estab-lished because

Page 321

362Connection Status Codes and Error Processing Section 14-301 0316 Error code returned from target:There was a parameter error in the frame used to c

Page 322

363Connection Status Codes and Error Processing Section 14-3Unique OMRON Error Codes01 0810 Error code returned from target:New data could not be obta

Page 323 - RECV(098) Instruction

13SECTION 2Unit SpecificationsThis section provides the specifications of EtherNet/IP Units and introduces recommended network configuration devices.

Page 324

364Error Log Function Section 14-414-4 Error Log FunctionErrors detected by the EtherNet/IP Unit or built-in EtherNet/IP port are storedin the error l

Page 325

365Error Log Function Section 14-414-4-4 Error Log Error CodesError code (hex)Error Detail code Saved in EEPROMFirst byte Second byte0001 CPU Unit wat

Page 326

366Error Log Function Section 14-40300 Parameter error; packet discarded FINS Command:Bit 15: OFFBits 08 to 14: Source network addressBits 00 to 07: S

Page 327 - FTP Server

367Error Log Function Section 14-403C4 Server connection error 00 hex: DNS03 hex: SNTP04 hex: FTP06 hex: BOOTP07 hex: SNMP08 hex: SNMP Trap01 hex: Spe

Page 328 - 11-1-1 Overview

368Troubleshooting Section 14-5Note If a memory error occurs in the error log area of EEPROM, the record will notbe stored in EEPROM.14-5 Troubleshoot

Page 329 - 11-2-1 File Types

369Troubleshooting Section 14-514-5-2 General Ethernet Problems14-5-3 Tag Data Links Fail to StartUse the following table to troubleshoot tag data lin

Page 330

370Troubleshooting Section 14-514-5-4 Tag Data Link ProblemsThe tag data isn't simultaneous.Observe the following precautions when writing applic

Page 331 - 11-3-1 Procedure

371Troubleshooting with FINS Response Codes Section 14-614-5-5 Message Timeout Problems14-6 Troubleshooting with FINS Response CodesThe cause of error

Page 332 - 11-3-3 FTP Tab

372Troubleshooting with FINS Response Codes Section 14-601 Local node error03 Local node send error--- Lack of available space in internal buffersThe

Page 333 - 230 Guest logged in

373Troubleshooting with FINS Response Codes Section 14-610 Command format error01 Command too long Command dataThe command is too long.Check the comma

Page 335

14EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-12-1 EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications2-1-1 Gene

Page 336

374Troubleshooting with FINS Response Codes Section 14-622 Status error(operating mode dis-agreement)0F Cannot execute because service is being proces

Page 337

375Appendix ACS/CJ-series Ethernet Unit Function ComparisonItem Support for functionEthernet Unit EtherNet/IP Unit or built-in EtherNet/IP portUnit ve

Page 338

376CS/CJ-series Ethernet Unit Function Comparison Appendix A

Page 339

377Appendix BEthernet Network ParametersNote The hold time is 3 s for the UCMM service, Class 3 service, and tag data link open/close processing.Param

Page 340 - FTP Status Flag

378Ethernet Network Parameters Appendix B

Page 341 - 11-7-2 File Types

379Appendix CTCP Status TransitionsThe TCP socket status can be confirmed using the socket status data returned for the FINS commandSOCKET STATUS READ

Page 342

380TCP Status Transitions Appendix C

Page 343 - .IOM file contents

381Appendix DCIP Message CommunicationsThis appendix describes CIP message communications.The basic concepts of CIP message communications are describ

Page 344 - ■ CSV Format

382CIP Message Communications Appendix DTerminologyIn CIP specifications, “Object,” “Class,” “Instance,” “Attribute” and “Service” are defined as foll

Page 345

383CIP Message Communications Appendix DRoute PathRoute PathIn the CIP, unlike the internet protocol, the transmission frame contains a complete relay

Page 346 - 11-8 FTP File Transfer Time

15EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1CJ-series EtherNet/IP UnitNote If tag data links are being used, use 100Bas

Page 347 - ··· Login name

384CIP Message Communications Appendix DAccording to CIP Specifications, the Segment Type specifications are decided as follows:The specifications of

Page 348 - FTP ended

385CIP Message Communications Appendix DSpecify the size of Link Address when the Extended Link Address Size is set to “1.” The following diagramshows

Page 349 - SECTION 12

386CIP Message Communications Appendix DThe 8-bit logical address can be used for the Attribute ID. Use the Attribute ID when requesting a Service of

Page 350 - EtherNet/IP Unit or

387CIP Message Communications Appendix DResponse CodesGeneral Status CodeThe General Status Code is stored in the response data after execution of the

Page 351 - 12-2-1 Procedure

388CIP Message Communications Appendix D1D Invalid attribute value listThe service is returning the list of attributes supplied with status informatio

Page 352

389CIP Message Communications Appendix DExample of Additional Status in case that General Status Is 01 Hex.(Status of Connection Manager Object)Genera

Page 353 - 12-2-3 Auto Adjust Time

390CIP Message Communications Appendix DPriority/Time Ticks and Time Out TicksFormat of the Priority/Time TickTime tick Base value (ms) Maximum time-o

Page 354 - Function

391Appendix EFINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports RESETResets the EtherNet/IP Unit or built-in EtherNet/IP port.

Page 355

392FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EPrecautions• No response will be returned if the command ends

Page 356

393FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EMode Setting (Response)The mode setting in the system setup is

Page 357 - SECTION 13

16EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1CJ2 CPU Built-in EtherNet/IP PortNote If tag data links are being used, use

Page 358 - 13-1-2 Inspection

394FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse CodesCONTROLLER STATUS READReads the controller statu

Page 359 - 13-2 Simple Backup Function

395FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EIP Router Table Error Routing Table ErrorEthernet Advanced Set

Page 360

396FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix ETotal Number of Packets Sent (Response)The total number of pac

Page 361 - DIP switch settings

397FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse CodesBROADCAST TEST RESULTS READReads the results (nu

Page 362 - 13-3 Using the Backup Tool

398FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EPrecautions• No response is made to this command. • When using

Page 363

399FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EError Code, Detailed InformationDetails of the error stored in

Page 364

400FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix ECommand BlockResponse BlockParametersDestination IP Address (C

Page 365 - SECTION 14

401FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix ECommand BlockResponse BlockParametersFINS/TCP Connection No. (

Page 366

402FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse BlockParametersFINS/TCP Connection No. (Command, Resp

Page 367

403FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse CodesIP ADDRESS TABLE WRITEWrites the IP address tabl

Page 368

17EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-12-1-3 Communications SpecificationsItem CS1/CJ1 CJ2H CJ2MCIP serviceTag dat

Page 369

404FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E• An error response will be returned if the IP address convers

Page 370

405FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse CodesPrecautions• The local IP address and subnet mas

Page 371

406FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EFINS Node AddressNode address for communications via the FINS

Page 372

407FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EMaximum Number of Stored Records (Response)The maximum number

Page 373

408FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EParametersIP Status (Response)Twelve types of IP status inform

Page 374

409FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E5. The number of received ICMP packets discarded because the t

Page 375

410FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E1. The number of times active connections were correctly estab

Page 376

411FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E8. The number of bytes in the resend packets. 9. The number of

Page 377

412FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EResponse BlockParametersMemory Status (Response)A total of 23

Page 378 - Data Links

413FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EPrecautionsAll the above values are set to 0 if Ethernet commu

Page 379 - Errors Related to Memory

18EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1Note (1) In this case, pps means “packets per second” and indicates the num

Page 380

414FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix ERemote Port Number (4 bytes)The remote port number allocated t

Page 381 - Errors Related to the

415FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EAddress InformationReturns the FINS node addresses and IP addr

Page 382

416FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EIP Address (Response)The local IP address set in the CPU Bus U

Page 383

417FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EDescriptionFor details, refer to EXPLICIT MESSAGE SEND (28 01)

Page 384

418FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix EDescriptionFor details, refer to CIP UCMM MESSAGE SEND (28 10)

Page 385 - WEB www.odva.org

419Appendix FEDS File ManagementThis section explains the EDS file management functions used in the Network Configurator.Installing EDS FilesNote Usin

Page 386

420EDS File Management Appendix F3. Select the EDS file to be installed and click the Open Button.Next, select the icon file (*.ico), and the EDS file

Page 387

421EDS File Management Appendix F3. Input the folder and file names and click the Save Button The EDS file will be saved. Searching EDS Files EDS File

Page 388

422EDS File Management Appendix F2. Select EDS File - Property.The following window will be displayed.The time and date that the EDS file was created

Page 389

423Appendix GPrecautions for Using Windows XP, Vista, or Windows 7Changing Windows Firewall SettingsBetter firewall security for Windows XP (SP2 or hi

Page 390 - 14-4 Error Log Function

19EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-12-1-4 DimensionsCS1W-EIP21CJ1W-EIP21CJ2H-CPU@@-EIP101 mm35 mm130 mmNODENO.1

Page 391 - 14-4-4 Error Log Error Codes

424Precautions for Using Windows XP, Vista, or Windows 7 Appendix GThe User Account Control Dialog Box may be displayed during this procedure. If it a

Page 392

425Precautions for Using Windows XP, Vista, or Windows 7 Appendix GAn EtherNet/IP connection will be accepted from CX-Programmer or Network Configurat

Page 393

426Precautions for Using Windows XP, Vista, or Windows 7 Appendix G

Page 394 - 14-5 Troubleshooting

427IndexNumerics7-segment display, 24AAdjust Time field, 326, 328alternate DNS server, 54applicationsprecautions, xxivAuto Adjust Time field, 326, 327

Page 395 - Troubleshooting Section 14-5

428Indexcreating a tag set, 126creating tag sets, 126creating tags, 128crimp terminals, xxvcurrent consumptionCJ-series, 15, 16CS-series, 14CX-Integra

Page 396 - 14-5-4 Tag Data Link Problems

Index429EtherNet/IP Unit Features, 2EtherNet/IP Unitsresetting, 391ETN11-compatible mode, 99explicit message communications, 187, 233explicit message

Page 397 - Relay Error Flag

430IndexHost name field, 326, 327II/O allocationsCIO Area, 70DM Area, 83I/O memory address, 116I/O response time, 283I/O tablescreating, 46overview, 4

Page 398

Index431multicast communications, 114multicast filter, 29Nnbeginning word of allocated CIO Area, 70networkdevices required for constructing a network,

Page 399

432Indexrefresh cycle, 268Register Device List, 141Registered Target Node Flags, 81, 85registering devices, 125, 141relay tables, 207rename command, 3

Page 400

Index433specifications, 115status flags, 186tag data links (cyclic communications), 6tag set, 116tag setscreating, 126Target Node PLC Error Flags, 73,

Page 401 - Appendix A

20EtherNet/IP Unit and Built-in EtherNet/IP Port Specifications Section 2-1CJ2M-CPU3@2-1-5 Software Configuration76.16 mm62 mm2.7 mm2.7 mm90 mm84.5 mm

Page 402

434Index

Page 403 - Appendix B

435Revision HistoryA manual revision code appears as a suffix to the catalog number on the front cover of the manual. The following table outlines the

Page 404

436Revision History

Page 406

Authorized Distributor:In the interest of product improvement, specifications are subject to change without notice.Cat. No. W465-E1-05Printed in Japan

Page 407 - Appendix D

21Nomenclature and Functions Section 2-22-2 Nomenclature and Functions2-2-1 Nomenclature and FunctionsCS1W-EIP21CJ1W-EIP21LED IndicatorsUnit numberset

Page 408 - Terminology

22Nomenclature and Functions Section 2-2Built-in EtherNet/IP Port in CJ2H-CPU@@-EIPBuilt-in EtherNet/IP Port in CJ2M-CPU3@Ethernet Address Notation A

Page 409 - Route Path

23Nomenclature and Functions Section 2-2Indicators A EtherNet/IP Units or built-in EtherNet/IP port is equipped with the followingindicators that indi

Page 410 - Port Segment

vNotice:OMRON products are manufactured for use according to proper procedures by a qualified operatorand only for the purposes described in this manu

Page 411 - Logical Segment

24Nomenclature and Functions Section 2-2Seven-segment Display When the power is turned ON (or the Unit is restarted), all of the segments willflash tw

Page 412 - Setting the Route Path

25Nomenclature and Functions Section 2-2If an error occurs, the error code will be displayed alternately with the right-most byte of the affected devi

Page 413 - Response Codes

26Nomenclature and Functions Section 2-2Right and Left Dot LEDsIf an error occurred in two or more devices with the same rightmost byte intheir IP add

Page 414

27Nomenclature and Functions Section 2-2Node Address Setting SwitchThe Node Address Setting Switch sets the node address of the EtherNet/IPUnit or bui

Page 415

28Selecting the Network Devices Section 2-32-3 Selecting the Network Devices2-3-1 Recommended Network DevicesThe following table shows the devices rec

Page 416

29Selecting the Network Devices Section 2-32-3-4 Switching Hub FunctionsThis section describes the switching hub functions that are important whenusin

Page 417 - Appendix E

30Selecting the Network Devices Section 2-3When selecting a switching hub, it is necessary to consider whether theswitching hub will be selected based

Page 418 - Command code

31Selecting the Network Devices Section 2-3L3 Switching Hub with Multicast Filtering and L4 QoS FunctionsWe recommend this kind of switching hub when

Page 419 - Ethernet Address (Response)

32Selecting the Network Devices Section 2-3

Page 420 - CONTROLLER STATUS READ

33SECTION 3Installation and Initial SetupThis section explains how to install and make the initial settings required for operation of the EtherNet/IP

Page 422 - 1,998 bytes max

34Overview of Initial Setup Procedures Section 3-13-1 Overview of Initial Setup Procedures3-1-1 ProceduresInitial Settings1,2,3... 1. Set the unit num

Page 423 - BROADCAST DATA SEND

35Overview of Initial Setup Procedures Section 3-19. Test communications.Send a PING command to the EtherNet/IP Unit or built-in EtherNet/IP port.Refe

Page 424 - ERROR LOG READ

36Switch Settings Section 3-23-2 Switch Settings3-2-1 CS-series EtherNet/IP UnitsSetting the Unit NumberThe unit number is used to identify individual

Page 425 - ERROR LOG CLEAR

37Switch Settings Section 3-23-2-2 CJ-series EtherNet/IP Units and CJ2 Built-in EtherNet/IP PortSetting the Unit NumberThe unit number is used to iden

Page 426 - Response Block

38Mounting to a PLC Section 3-33-3 Mounting to a PLC3-3-1 Mounting to a CS-series PLCEtherNet/IP Units can be mounted to any slot in a CS-series CPU R

Page 427

39Mounting to a PLC Section 3-3Note The CJ1W-EIP21 EtherNet/IP Unit’s maximum current consumption is410 mA. Be sure that the total current consumption

Page 428

40Mounting to a PLC Section 3-33. When removing the Unit, first loosen the screw at the bottom of the Unit.Note When mounting the Unit, provide the cl

Page 429 - IP ADDRESS TABLE WRITE

41Network Installation Section 3-43-4 Network Installation3-4-1 Basic Installation Precautions• Take the greatest care when installing the Ethernet Sy

Page 430 - IP ADDRESS WRITE

42Network Installation Section 3-4• Press the cable connector in firmly until it locks into place at both theswitching hub and the EtherNet/IP Unit.•

Page 431 - IP ADDRESS TABLE READ

43Network Installation Section 3-4Note Best = Recommended; OK = Allowed; --- = Not allowed.3-4-4 Using Contact Outputs (Common to All Units)When an Et

Page 432 - IP ROUTER TABLE READ

viiTABLE OF CONTENTSPRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xxi1 Intended Audience. . . . . . . . . . . . .

Page 433 - PROTOCOL STATUS READ

44Connecting to the Network Section 3-53-5 Connecting to the Network3-5-1 Ethernet ConnectorsThe following standards and specifications apply to the c

Page 434

45Connecting to the Network Section 3-51,2,3... 1. Lay the twisted-pair cable.2. Connect the cable to the switching hub. Be sure to press in the cable

Page 435 - TCP Status (Response)

46Creating I/O Tables Section 3-63-6 Creating I/O Tables3-6-1 I/O Table OverviewI/O tables are used to identify Units mounted to the PLC, and to alloc

Page 436

47Creating I/O Tables Section 3-6(2) With the CJ2H-CPU@@-EIP and CJ2M-CPU3@ CPU Units, the built-inEtherNet/IP port is set in the I/O tables by defaul

Page 437 - MEMORY STATUS READ

48Creating I/O Tables Section 3-62. The Direct Online Dialog Box will be displayed. Select a serial connection,select the name of the applicable compu

Page 438

49Creating I/O Tables Section 3-65. The EtherNet/IP Unit will be displayed at the position it is mounted in thePLC.Note If it is not displayed, select

Page 439 - Command

50Setting the Local IP Address Section 3-73-7 Setting the Local IP AddressThis section describes the 3 ways to set the local I/O address of an EtherNe

Page 440 - ADDRESS INFORMATION READ

51Setting the Local IP Address Section 3-7Method 2: Setting the Address in the CPU Bus Unit's Allocated DM AreaWith this method, an IP address is

Page 441 - IP ADDRESS READ

52TCP/IP and Link Settings Section 3-83-8 TCP/IP and Link SettingsThis section describes the TCP/IP-related settings, such as the local IPaddress and

Page 442 - EXPLICIT MESSAGE SEND

53TCP/IP and Link Settings Section 3-84. Place the CX-Programmer online with the PLC and transfer the settings tothe EtherNet/IP Unit or built-in Ethe

Page 443 - CIP UCMM MESSAGE SEND

viiiTABLE OF CONTENTSSECTION 4Memory Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 674-1 Overview of Memory Allocated to

Page 444 - Description

54TCP/IP and Link Settings Section 3-8IP AddressSets the local IP address of the EtherNet/IP Unit or built-in EtherNet/IP port.Set the local IP addres

Page 445 - Appendix F

55TCP/IP and Link Settings Section 3-8functions that require a DNS server, so these settings are not used. (Thefunctionality required to use a DNS ser

Page 446 - Saving EDS Files

56TCP/IP and Link Settings Section 3-82. Select Tools - Setup TCP/IP Configuration to display the following SetupTCP/IP Configuration Dialog Box, and

Page 447 - Searching EDS Files

57Tag Data Link Parameters Section 3-9Configurator, connect the devices one at a time, and download the TCP/IP Configuration’s IP address parameters.

Page 448

58Tag Data Link Parameters Section 3-9The following method can be used to easily set the data links shown in the fol-lowing figure using a wizard in t

Page 449 - Appendix G

59Tag Data Link Parameters Section 3-93. Select Datalink − Wizard from the menus in the Datalink Tool when it hasstarted. 4. In the Datalink Wizard Di

Page 450

60Tag Data Link Parameters Section 3-96. In the Device Configuration Window of the Network Configurator, a mark will be added to each EtherNet/IP Unit

Page 451

61Other Parameters Section 3-103-10 Other ParametersIn addition to the tag data link parameters, the EtherNet/IP Unit and built-inEtherNet/IP port als

Page 452

62Other Parameters Section 3-10Using FINS/TCPWhen necessary, set the routing tables using the CX-Integrator.Using FTPTab Page in Edit Parameters Dialo

Page 453 - Numerics

63Other Parameters Section 3-10Using the Automatic Time AdjustmentUsing the Status AreaTab Page in Edit Parameters Dialog BoxSetting FunctionAuto Adju

Page 454

ixTABLE OF CONTENTSSECTION 10Communications Performance and Communications Load 26110-1 Communications System . . . . . . . . . . . . . . . . . . . .

Page 455

64Other Parameters Section 3-10Using SNMPUsing SNMP TrapTab Page in Edit Parameters Dialog BoxSetting FunctionSNMP Not use SNMP service orUse SNMP ser

Page 456

65Communications Test Section 3-113-11 Communications TestIf the basic settings (in particular the IP address and subnet mask) have beenmade correctly

Page 457

66Communications Test Section 3-11Application ExampleIn this example, a PING command is sent to the node at IP address130.25.36.8. The “$” in the exam

Page 458

67SECTION 4Memory AllocationsThis section describes the words allocated in the CIO Area and the DM Area for EtherNet/IP Units or built-in EtherNet/IPp

Page 459

68Overview of Memory Allocated to the EtherNet/IP Unit Section 4-14-1 Overview of Memory Allocated to the EtherNet/IP UnitThe following CPU Unit words

Page 460

69Overview of Memory Allocated to the EtherNet/IP Unit Section 4-1CPU Unit● Allocated CIO Area words (Allocated to the Unit as a CPU Bus Unit.)100 wor

Page 461 - Revision History

70CIO Area Allocations Section 4-24-2 CIO Area Allocations4-2-1 Overview of the Allocated CIO Area WordsThe various kinds of data are stored in the a

Page 462

71CIO Area Allocations Section 4-2User SettingsNote The reserved words are regularly refreshed with all zeroes.The functions of the allocated CIO Area

Page 463

72CIO Area Allocations Section 4-2Tag Data Link Start Bit(Bit 2)Start the tag data links by switching this bit from OFF to ON. If the tag datalinks ar

Page 464 - Contact: www.ia.omron.com

73CIO Area Allocations Section 4-2Target Node PLC Error Information (EtherNet/IP Unit to CPU Unit) (n + 6 to n + 9)These words show the error status (

Commentaires sur ces manuels

Lynwood 14 Mar 2024 | 16:50:43

How To Create An Awesome Instagram Video About Pornstars On Adultwork British Porn Stars Xxx (Https://Qooh.Me)