363
Connection Status Codes and Error Processing Section 14-3
Unique OMRON Error Codes
01 0810 Error code returned from target:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
This error may
occur if the CPU
Unit’s cycle time
was long when
opening the con-
nection, the speci-
fied EM bank was
converted to file
memory, or some
problem in the
PLC caused the
PLC to stop.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data. If the PLC
has stopped,
identify and cor-
rect the error.
If the PLC system
is stopped, iden-
tify the cause of
the error from the
CPU Unit error
data.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the origi-
nator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer.)
01 0811 Error code generated in origina-
tor:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
This error may
occur if the CPU
Unit’s cycle time
was long when
opening the con-
nection, or the
specified EM bank
was converted to
file memory.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the origi-
nator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer.)
Connection status Source of error Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1 Configuration 2 Configuration 3
Vue de la page 388
1 2 ... 384 385 386 387 388 389 390 391 392 393 394 ... 463 464

Commentaires sur ces manuels

Lynwood 14 Mar 2024 | 16:50:43

How To Create An Awesome Instagram Video About Pornstars On Adultwork British Porn Stars Xxx (Https://Qooh.Me)