Using FINS Applications Section 8-5
8-5-2 FinsGateway
FinsGateway Ver. 2003 must be used to communicate using FINS/TCP
between applications serving as communications drivers and CS1W-EIP21,
CJ1W-EIP21, CJ2H-CPU@@-EIP, or CJ2M-CPU3@ EtherNet/IP Units.
FinsGateway Ver. 3.@ or lower versions can be used, however, when commu-
nicating by the FINS/UDP method only.
Overview of Setup Methods
1. Starting FinsGateway Settings
Select FinsGateway FinsGateway Setup to start the FinsGateway Setup.
2. ETN_UNIT Driver Setup
1. Double-click on ETN_UNIT in the settings for the network and Unit. The fol-
lowing ETN_UNIT Properties Window will be displayed.
• Network Tab Page
Network number Set the network number for the personal computer
(Ethernet port).
Local node address Set the personal computer (Ethernet port) node
address (1 to 254) on the Ethernet network.
Communication unit number Set the unit number in decimal (16 to 31) for the per-
sonal computer (Ethernet port).